How glazing ratios are calculated
Learn how PreDesign calculates the recommended maximum glazing ratios in the Glazing Ratio feature. This article covers:
- The approach and how it draws on ASHRAE 90.1.
- How PreDesign calculates the recommended maximum glazing ratio for cold weather.
- How PreDesign calculates the recommended maximum glazing ratio for harmful direct sun.
- How PreDesign combines these limits.
The recommendations draw mainly on ASHRAE 90.1 (2017). They assume you want the facade to match the performance of a baseline building facade.
For more detail, see:
Strategy scoring
Glazing Ratio gives each strategy a recommended maximum glazing percentage. In the example below, the 4 strategies have maximum ratios ranging from 22% to 56%. The options always appear from highest to lowest.

Feature design philosophy
ASHRAE 90.1 includes a method for comparing a proposed design with a baseline version of the same design.
The proposed design passes the standard if it performs at least as well as the baseline. This usually requires a full energy calculation. At the PreDesign stage, you do not yet have a 3D design and may not have someone available to calculate energy use.
Glazing Ratio estimates the maximum glazing area that would match an ASHRAE 90.1 baseline. This assumes all other factors are equal.
PreDesign calculates this as follows:
- PreDesign identifies the study's ASHRAE climate zone from the location you enter.
- PreDesign calculates the baseline facade's overall insulation values using the standard. It then calculates glazing ratios for combinations that would match those values.
- PreDesign calculates a solar heat gain score for the whole baseline facade. It then identifies shading and glazing combinations that would match that score.
- PreDesign compares the insulation and solar control limits. The more restrictive limit becomes the recommended maximum glazing ratio.
How it works in cold weather
PreDesign uses the standard to find 3 values for the baseline model:
- The baseline glazing ratio, set at 40% for all options.
- The baseline glazing assembly U-value, which measures insulation across the whole window system.
- The baseline wall assembly U-value, which measures insulation across the whole wall system.
These values depend on building type and climate zone. Orientation does not affect the cold weather calculation. PreDesign leaves out this calculation in climate zones with no winter.
PreDesign then calculates an effective baseline U-value for the whole facade assembly.
For each strategy, PreDesign determines:
- The glazing assembly U-value, based on the frame and glazing type. PreDesign calculates this using LBNL's Window 7 software. All assembly options are available on request.
- The wall assembly U-value, assumed to match the baseline model.
PreDesign uses these values to calculate the glazing percentage that would match the baseline's whole facade assembly U-value. This percentage becomes the maximum glazing ratio for insulation.
How it works for direct sun
PreDesign first checks whether direct sun is a problem for each facade orientation.
It uses the same method to decide whether the facade needs shading. The shading guidance explains this method in full.
PreDesign uses the following calculation:
- Determine the Balance Point Temperature from the building type.
- Classify the time step as "overheating" if the outside temperature is at least 2°C above the Balance Point Temperature.
- Increase the effective outside temperature if solar radiation is intense.
- Calculate the difference between the effective outside temperature and the balance point temperature.
- Adjust this difference for the sun's angle of incidence on the facade at that time.
- Calculate a "degree-hours of overheating" value for that time step.
- Add the "degree-hours of overheating" values for the whole year.
The total must exceed the threshold in the table below for direct sun to count as a problem.
If direct sun is a problem, PreDesign continues the assessment. Otherwise, direct sun does not affect the glazing ratio for that orientation.
If direct sun is a problem, PreDesign uses the standard to find 2 values for the baseline model:
These values depend on building type and climate zone, but not orientation. PreDesign then makes the following calculations:
- PreDesign uses these values to calculate an effective baseline SHGC for the whole facade assembly.
- For each strategy, PreDesign calculates the effective glazing SHGC from the glazing's solar control properties.
- PreDesign reduces this value according to the shading type:
- Reduce by 0% with no shading.
- Reduce by 25% with partial shading.
- Reduce by 50% with substantial shading.
- Reduce by 75% with extensive shading.
- PreDesign then compares the strategy's effective glazing assembly SHGC with the baseline's effective facade SHGC.
PreDesign assumes the opaque facade has an SHGC of 0%. It uses these values to calculate the glazing percentage that would match the baseline's effective facade SHGC. This percentage becomes the maximum glazing ratio for solar control.
Reference tables
Use these tables to look up the baseline values used in the calculations.
Climate zones
The climate zones in the table below are calculated from ASHRAE Standard 169-2013.

Baseline properties
Glazing and wall assembly U-values and baseline glazing SHGC values come from ASHRAE 90.1 (2019).
Non-residential
Climate Zone | Code Glazing | Code Wall | Code Glazing |
|---|---|---|---|
0A | 2.84 | 0.504 | 0.22 |
0B | 2.84 | 0.504 | 0.22 |
1A | 2.84 | 0.504 | 0.23 |
1B | 2.84 | 0.504 | 0.23 |
2A | 2.56 | 0.504 | 0.25 |
2B | 2.56 | 0.504 | 0.25 |
3A | 2.38 | 0.504 | 0.25 |
3B | 2.38 | 0.504 | 0.25 |
3C | 2.38 | 0.504 | 0.25 |
4A | 2.04 | 0.365 | 0.36 |
4B | 2.04 | 0.365 | 0.36 |
4C | 2.04 | 0.365 | 0.36 |
5A | 2.04 | 0.291 | 0.38 |
5B | 2.04 | 0.291 | 0.38 |
5C | 2.04 | 0.291 | 0.38 |
6A | 1.93 | 0.153 | 0.38 |
6B | 1.93 | 0.153 | 0.38 |
7A | 1.65 | 0.291 | 0.4 |
7B | 1.65 | 0.291 | 0.4 |
8A | 1.48 | 0.182 | 0.4 |
8B | 1.48 | 0.182 | 0.4 |
Residential
Climate Zone | Code Glazing | Code Wall | Code Glazing |
|---|---|---|---|
0A | 3.52 | 0.504 | 0.2 |
0B | 3.52 | 0.504 | 0.2 |
1A | 3.52 | 0.504 | 0.21 |
1B | 3.52 | 0.504 | 0.21 |
2A | 3.41 | 0.504 | 0.23 |
2B | 3.41 | 0.504 | 0.23 |
3A | 3.07 | 0.365 | 0.23 |
3B | 3.07 | 0.365 | 0.23 |
3C | 3.07 | 0.365 | 0.23 |
4A | 2.56 | 0.365 | 0.33 |
4B | 2.56 | 0.365 | 0.33 |
4C | 2.56 | 0.365 | 0.33 |
5A | 2.56 | 0.291 | 0.33 |
5B | 2.56 | 0.291 | 0.33 |
5C | 2.56 | 0.291 | 0.33 |
6A | 2.38 | 0.153 | 0.34 |
6B | 2.38 | 0.153 | 0.34 |
7A | 2.04 | 0.291 | 0.36 |
7B | 2.04 | 0.291 | 0.36 |
8A | 1.82 | 0.182 | 0.36 |
8B | 1.82 | 0.182 | 0.36 |
Calculated baseline U-values and SHGCs for the whole wall. All values assume 40% glazing.
Non-residential
Climate Zone | Assembly Baseline | Assembly Baseline |
|---|---|---|
0A | 1.4384 | 0.088 |
0B | 1.4384 | 0.088 |
1A | 1.4384 | 0.092 |
1B | 1.4384 | 0.092 |
2A | 1.3264 | 0.1 |
2B | 1.3264 | 0.1 |
3A | 1.2544 | 0.1 |
3B | 1.2544 | 0.1 |
3C | 1.2544 | 0.1 |
4A | 1.035 | 0.144 |
4B | 1.035 | 0.144 |
4C | 1.035 | 0.144 |
5A | 0.9906 | 0.152 |
5B | 0.9906 | 0.152 |
5C | 0.9906 | 0.152 |
6A | 0.8638 | 0.152 |
6B | 0.8638 | 0.152 |
7A | 0.8346 | 0.16 |
7B | 0.8346 | 0.16 |
8A | 0.7012 | 0.16 |
8B | 0.7012 | 0.16 |
Residential
Climate Zone | Assembly Baseline | Assembly Baseline |
|---|---|---|
0A | 1.7104 | 0.08 |
0B | 1.7104 | 0.08 |
1A | 1.7104 | 0.084 |
1B | 1.7104 | 0.084 |
2A | 1.6664 | 0.092 |
2B | 1.6664 | 0.092 |
3A | 1.447 | 0.092 |
3B | 1.447 | 0.092 |
3C | 1.447 | 0.092 |
4A | 1.243 | 0.132 |
4B | 1.243 | 0.132 |
4C | 1.243 | 0.132 |
5A | 1.1986 | 0.132 |
5B | 1.1986 | 0.132 |
5C | 1.1986 | 0.132 |
6A | 1.0438 | 0.136 |
6B | 1.0438 | 0.136 |
7A | 0.9906 | 0.144 |
7B | 0.9906 | 0.144 |
8A | 0.8372 | 0.144 |
8B | 0.8372 | 0.144 |